Performance maps for an air-cooled air conditioning system as a preliminary instrument for the diagnosis of evaporator fouling

2019

Abstract During the past few decades, there has been increased interest in the development of automated approaches for detecting and diagnosing faults in air conditioning systems. Among them, thermoeconomic diagnosis is a technique which involves the use of exergy analysis. As a first step towards improving its performance, this work is focused on the thermodynamic and exergy analysis of a direct expansion air conditioning system used in small commercial building applications. The analysis was carried out by means of experimental activities on a 17.5 kW rooftop unit installed at the Herrick Laboratories, Purdue University, Indiana (USA). The system under investigation was equipped with a va…

ExergyHistoryWork (thermodynamics)Foulingbusiness.industryCooling loadFault (power engineering)Computer Science ApplicationsEducationAir conditioningEnvironmental sciencebusinessProcess engineeringGas compressorEvaporatorJournal of Physics: Conference Series
researchProduct

Thermoeconomic diagnosis of air conditioning systems: experimental assessment of performance for improved reliability

2018

Thermoeconomic diagnosis is an exergy-based fault detection and diagnosis technique which has been recently extended to air conditioning systems. So far, developments of this technique have relied only on simulation data without being evaluated using real data. For the first time, this work aims at assessing the performance of thermoeconomic diagnosis using experimental data obtained from a five-ton packaged rooftop air conditioning unit (RTU) installed at Herrick Laboratories, Purdue University. The RTU was tested in psychrometric chambers under a wide range of operating conditions and fault levels. The following faults were investigated: (i) evaporator fouling, (ii) condenser fouling and …

Thermoeconomic Diagnosis exergy direct expansion coil evaporator fouling condenser fouling multiple faultsSettore ING-IND/10 - Fisica Tecnica Industriale
researchProduct

Performance maps for an air-cooled air conditioning system as a preliminary instrument for the diagnosis of evaporator fouling

2018

During the past few decades, there has been increased interest in the development of automated approaches for detecting and diagnosing faults in air conditioning systems. One diagnostic approach involves the use of exergy analysis. As a first step towards understanding the application of exergy analysis to diagnostics, this work is focused on the thermodynamic and exergy analysis of a direct expansion air conditioning system used in small commercial building applications. The analysis was carried out by means of experimental activities on a 17.5 kW rooftop unit installed at the Herrick Laboratories, Purdue University, Indiana (USA). The system under investigation was equipped with a variabl…

Settore ING-IND/10 - Fisica Tecnica IndustrialeDirect expansion coil thermoeconomic diagnosis exergy performance map evaporator fouling
researchProduct