0000000000386720

AUTHOR

Artale G.

showing 4 related works from this author

Measurement issues on harmonic analysis according to the IEC 61000-4-7

2022

The objective of this article is an analysis of measurement issues related to the implementation of digital signal processing techniques for harmonic analysis, by means of FFT algorithm with different interpolation algorithms (linear, quadratic and cubic) and different sampling rates. A comparative analysis is made on errors on harmonics measurement obtained in the various case study analyses. Such errors are compared with the IEC 61000-4-7 limits. The study is supported by both simulation and experimental tests; these last are performed with different acquisition boards for signals acquisition.

Harmonic analysisIEC 61000-4-7power qualitypower system measurementsSettore ING-INF/07 - Misure Elettriche E Elettroniche
researchProduct

A single-point approach based on nonactive power factor for the assessment of harmonic distortion sources in power systems

2022

This paper presents a study on the use of power factor indicators for the assessment of harmonic distortion sources in power systems. In detail the analysis is focused on the comparison between the proposed nonactive power factor (Q1/N) and the indicators of the IEEE Std. 1459-2010, and on the indicators feasibility in identifying the presence of harmonic distortion sources. As discussed in the paper, the proposed indicator can be evaluated with good accuracy, by means of typical power quantities measurements at the point of common coupling (PCC). Thus its measurement can be feasibly implemented in commercial platforms used for smart metering applications. To verify the proposal validity, s…

IEEE 1459-2010Power QualityPower Ratio QuantitiesSettore ING-INF/07 - Misure Elettriche E Elettroniche2022 IEEE International Instrumentation and Measurement Technology Conference (I2MTC)
researchProduct

Impact of non-programmable distributed generation in an islanded microgrid: the case study of Ustica

2022

The paper presents a systematic analysis of nonprogrammable distributed generation impact in an islanded microgrid Different issues have been analyzed, with a special focus on the most significant ones in a small islanded network. To this aim, the case study of Ustica island was considered A digital twin of the MV network was developed starting from the network topology data and the power measurement acquired in each secondary substation. Simulations were then performed in the hypothesis of a large increment of distributed generation installation into the network. A discussion is then reported on which are the main technical issues to be faced in the considered case study.

smart-gridgrid stabilityDistributed generationSettore ING-INF/07 - Misure Elettriche E Elettroniche2022 IEEE 21st Mediterranean Electrotechnical Conference (MELECON)
researchProduct

Time domain symmetry parameters analysis for series arc fault detection

2022

This paper presents a feasibility study of exploiting the symmetry of some parameters for series arc fault detection in electrical circuits. The considered parameters are defined in the time domain and they are based on the current signal derivative and the evaluation of cross-correlation between subsequent observation windows. The analysis is carried out for AC systems, starting from an experimental characterization, which has been carried out in accordance with the Standard UL 1699 requirements for "unwanted tripping tests"and "operation inhibition tests"of arc fault circuit interrupters (AFCIs). The results obtained in different load conditions show that the proposed parameters can be us…

series arcsarc faults detectionelectrical safetyUL 1699power system measurementsSettore ING-INF/07 - Misure Elettriche E ElettronicheArc fault circuit interrupter (AFCI)2022 IEEE 12th International Workshop on Applied Measurements for Power Systems (AMPS)
researchProduct