Characteristics of partial discharges in an experimental setup reproducing HVDC cable insulation operating conditions
The occurrence of Partial Discharge (PD) inside a cavity subjected to HVDC voltage can be considered as one of the most likely sources of insulation ageing and failure. In practical applications, the recognition of PD under HVDC is more difficult than under AC stress because of the lower repetition rates and the impossibility to obtain a PD pattern synchronized with the waveform of the applied voltage. In this paper, the relationship between conduction phenomena in dielectrics and the occurrence of PD is investigated by means of a novel experimental setup. A couple of dielectric cells connected in series is subjected to various HVDC stress levels. The applied voltage is divided between the …