6533b825fe1ef96bd1281fce

RESEARCH PRODUCT

Frequency response of Measurement Current Transformers

Salvatore NuccioDario Di CaraA.e. EmanuelAntonio CataliottiP.a. Di Franco

subject

Frequency responseTotal harmonic distortionMaterials scienceTransducerlawPower system harmonicsElectronic engineeringEquivalent circuitIec standardsTransformerCurrent transformerHardware_LOGICDESIGNlaw.invention

description

In this paper the frequency response of two CTs is experimentally evaluated in the range of 30-600 Hz. A theoretical analysis of CTs behavior has been developed by means of the equivalent circuit. It was shown, by an experimental test, that, for the frequency range analyzed, the transformer equivalent circuit is a valid tool for the evaluation of CT performances.