6533b839fe1ef96bd12a5b93
RESEARCH PRODUCT
A New Measurement Method for the Detection of Harmonic Sources in Power Systems Based on the Approach of the IEEE Std. 1459–2000
Antonio CataliottiValentina Cosentinosubject
EngineeringTotal harmonic distortionbusiness.industrySystem of measurementEnergy Engineering and Power TechnologyAC powerlaw.inventionElectric power systemlawElectrical networkHarmonicElectronic engineeringUpstream (networking)Time domainElectrical and Electronic EngineeringbusinessSettore ING-INF/07 - Misure Elettriche E ElettronicheDetection of harmonic sources harmonic distortion IEEE Std. 1459–2000 power definitions power measurement power quality (PQ)description
In this paper, a novel single-point strategy is proposed for the detection of the harmonic sources in power systems. The method is an improvement of a strategy previously proposed by the authors; it is developed from the IEEE Std 1459-2000 approach and it can be entirely implemented in the time domain, thus simplifying the measurement system. The effectiveness of the proposed method is evaluated by introducing simple decision-making rules and by taking the presence of the measurement transducers into account. Several simulations and experimental tests are presented, showing that the enhanced strategy is able to give an useful information on the detection of the dominant harmonic source upstream or downstream the metering section.
year | journal | country | edition | language |
---|---|---|---|---|
2010-01-01 | IEEE Transactions on Power Delivery |