Search results for "ENERGIA"
showing 10 items of 1046 documents
A method for the evaluation of fault current distribution in complex high voltage networks
2015
Abstract The paper presents a method for the study of large interconnected earthing systems in High Voltage networks. The mathematical model proposed for calculating the distribution of the Single-line-to-Earth fault current is useful for a methodical and accurate analysis of complex systems having meshed configuration and more sources, and has practical application for the Transmission System Operator. Two case studies are provided. The first one considers a fault occurring inside and outside a station in a real 220 kV transmission network. In the second example, the proposed methodology is compared with the classical “Double-sided elimination” method.
A Compensation Based Method to Model PV Nodes in Backward/Forward Distribution Network Analysis
2007
PurposeThis paper proposes to identify a new model of the fixed voltage nodes (PV nodes) for medium voltage distribution systems analysis. The model is used within backward/forward (b/f) analysis method applied to solve radial and weakly meshed systems.Design/methodology/approachThe model is based on the compensation currents method for multi‐port systems which has been extensively used, within b/f analysis methods, to take into account the presence of meshes and PV nodes.FindingsTest results prove the approach to be more efficient and precise than previous methodologies and put into evidence the good performance of the proposed model in terms of speed and convergence properties.Research li…
Simple Circuit Models for Studying Global Earthing Systems
2007
The paper proposes three simple circuit models for the simulation of the behaviour of a global earthing system during different fault events. The models allow one the evaluation of the maximum earth potential rise at every possible fault location and for every possible fault event. The three considered fault events are: single-line-to-earth fault inside a MV/LV substation, double-earth-fault in a MV line, single-line-to-earth fault inside a HV/MV station. After having illustrated the hypotheses at the basis of the study, the circuit models for the three fault events are presented and a numerical example shows how to use them in order to check the "global safety" of the interconnected earthi…
Reliability Analysis of a Stand-Alone PV System for the Supply of a Remote Electric Load
2010
The work presents a reliability analysis of a stand-alone photovoltaic system for the supply of electric loads located in remote areas not easily reachable by the low voltage distribution network. The analysis is performed by characterizing the electric load behavior by means of a Montecarlo approach for taking into account the stochastic variability of the electrical energy demand. A Montecarlo approach is used also for evaluating the electricity production of the stand alone photovoltaic system as a function of the hourly solar irradiation of the installation site. The variability both of the load and of the energy production are correlated and the probability that the load can remain uns…
Overcoming synchronization issues in wireless technology Partial Discharge measurement
2016
In this paper, several aspects of the fundamentals of wireless Partial Discharge (PD) measurements are first discussed. Then, the relevance of the problem of voltage synchronization in PD wireless diagnosis is outlined. When portable instruments are used for PD detection, the main issue is the voltage measurement at the site where the PD detection is carried out. When such analysis is carried out over shielded cables, the AC (50/60 Hz) voltage reference signal is not easily detectable, while one of the basic parameters for PD diagnosis, the displacement of the inception voltage of the PD as compared to the reference voltage, is not available. Even if highperformance sensors are readily avai…
Lightning-current distribution in MV grids interconnected earthing systems
2017
The paper presents first investigations results on the effects of lightning stroke on medium voltage (MV) installations' earthing systems, connected together with the metal shields of the MV distribution grid cables. The study enables to evaluate the distribution of the lightning current among interconnected earth electrodes in order to assess if the interconnection, usually done for reducing earth potential rise during an earth fault, can give place to dangerous situations far from the installation hit by the lightning stroke. Two case studies of direct lightning stroke are presented and discussed: two interconnected MV substations of the MV grid; a high voltage/medium voltage (HV/MV) stat…
An experimental study on relationship between LED lamp characteristics and non image-forming
2017
The general aim of the experimental study, presented in this paper, was that to investigate the relationship between the characteristics of five different types of LED (Light Emitting Diode) lamps, which are nowadays those allowing the highest energy consumption reduction, and the humans non image-forming (NIF) reactions.
Active load sharing technique for on-line efficiency optimization in DC microgrids
2017
Recently, DC power distribution is gaining more and more importance over its AC counterpart achieving increased efficiency, greater flexibility, reduced volumes and capital cost. In this paper, a 24-120-325V two-level DC distribution system for home appliances, each including three parallel DC-DC converters, is modeled. An active load sharing technique is proposed for the on-line optimization of the global efficiency of the DC distribution network. The algorithm aims at the instantaneous efficiency optimization of the whole DC network, based on the on-line load current sampling. A Look Up Table, is created to store the real efficiencies of the converters taking into account components toler…
Optimizing droop coefficients for minimum cost operation of islanded micro-grids
2017
This paper shows how minimum cost energy management can be carried out for islanded micro-grids considering an expanded state that also includes the system's frequency. Each of the configurations outputted by the energy management system at each hour are indeed technically sound and coherent from the point of view of generation-consumption balancing by exploiting a frequency dependent load flow algorithm. A Glow-worm Swarm Optimization (GSO) algorithm carried out in a 24 hour time frame provides optimized results. A test has been carried out for a residential PV-Storage-Microturbine islanded micro-grid to show the feasibility as well as the efficiency of the proposed approach and results ar…
Smart district energy optimization of flexible energy units for the integration of local energy storage
2017
Several changes are involving electrical power systems, especially distribution networks. For this reason, the actors in charge of managing and operating reliably these grids are facing many technical issues regarding demand and supply balancing, Renewable Energy Sources and Electric Vehicles integration, peak load shaving, etc. In this context, many energy actions have been implemented for providing services to the power system managers by means of prosumers' demand and/or supply flexibility. This study reports the development of a centralized energy management solution for smart grids equipped with local storage devices, RES, consumers and other energy facilities in a district context. Th…