Search results for "R417A"

showing 4 items of 4 documents

On-site Experimental Study of HCFC-22 Substitution with HFCs Refrigerants

2012

Abstract The European Regulation no 2037/2000 has banned manufacturing HCFC refrigerants from January 1st 2010, although its use is allowed up to 2015 if the fluids come from a recycling process. This situation creates the need for developing new working fluids to replace the HCFC in the refrigeration plants now in operation. Among all the HCFCs the R22 is the most widely used in a wide range of applications, especially in air conditioning. This paper presents the results of an experimental analysis comparing the performance of a vapour compression refrigerating unit operating with R22, and its performance in comparison to some HFCs fluids, substituting the former. In particular, the plant …

Engineeringbusiness.industryHFCsRefrigerationThermodynamicsR22RefrigerantEnergy(all)Air conditioningSettore ING-IND/10 - Fisica Tecnica IndustrialeHfCR404AR417AR407CbusinessProcess engineeringEnergy Procedia
researchProduct

Experimental performance evaluation of a vapour compression refrigerating plant when replacing R22 with alternative refrigerants

2011

Abstract This paper presents the results of an experimental analysis comparing the performance of a vapour compression refrigerating unit operating with R22, and its performance in comparison to a new HFC fluid, substituting the former according to Regulation No 2037/2000. In particular, the plant working efficiency was first tested with R22 and then with three new HFC fluids: R417A, R422A and R422D. The investigation verified that despite the case of substitution and the advantage of being able to continue to use mineral oil as a lubricant in the compressor, the performance with the new tested fluids did not result as efficient as when using R22.

Engineeringbusiness.industryMechanical EngineeringAlternative refrigerantThermodynamicsBuilding and ConstructionManagement Monitoring Policy and LawCompression (physics)R22RefrigerantGeneral EnergyR422DmedicineSettore ING-IND/10 - Fisica Tecnica IndustrialeR417ALubricantMineral oilbusinessProcess engineeringR422AGas compressormedicine.drug
researchProduct

An experimental study of a refrigerating plant when replacing R22 with HFCs refrigerants

2011

This paper presents the results of an experimental analysis comparing the performance of a vapour compression refrigerating unit operating with R22, and its performance in comparison to some HFCs fluids, substituting the former according to reg. n. 2037/2000. In particular, the plant working efficiency was first tested with R22 and then with three HFC fluids: R417A, R407C and R404A. The investigation verified that the performance with HFCs refrigerants did not result as efficient as when using R22. An environmental analysis also was performed.

R407C R404A.Settore ING-IND/10 - Fisica Tecnica IndustrialeR417AR22
researchProduct

Use of HFC fluids as suitable replacements in low-temperature refrigeration plants

2014

An experimental investigation of the performance of a low-temperature refrigerating unit working with R22 and a comparison of its performance when operating with replacement HFC fluids in accordance with the European Regulation CE-1005/2009 are presented in this paper. Plant working efficiency was tested with R22, as baseline, and then compared with four different HFC fluids: R413A, R417A, R422A and R422D. The refrigerating unit was a vapour-compression plant equipped with a reciprocating double-cylinder compressor able to keep the cold room at -20ºC. Lower values of the temperature at the end of compression and polytrophic exponent can be achieved with the HFC tested. Substituting the R22 …

R422dSettore ING-IND/10 - Fisica Tecnica IndustrialeRefrigerating systemR417aR422aR22R413a
researchProduct