A novel approach to current transformer characterization in the presence of harmonic distortion
2009
The current transformer (CT) performance under distorted waveform conditions is usually characterized by means of the frequency-response test. In this paper, a new way to characterize CTs, closer to real operation conditions, is proposed. The harmonic phase-angle and ratio errors are measured using a nonsinusoidal current composed of fundamental and one harmonic with adjustable phase shift. The new method was tested by determining the performance of two metering class CTs commonly used by the Italian power company. The errors measured using the proposed approach are larger than the ones obtained with the frequency response. This result suggests that the frequency-response approach for the e…
Oil filled MV/LV Power Transformer Behavior in Narrow Band Power Line Communication Systems
2012
The aim of this paper is to characterize oil-filled power transformers in the narrow-band power-line communication (PLC) frequency range of 50-150 kHz. A new model is proposed for such type of a transformer, in the aforementioned frequency range of interest, in order to study its influence on the signal transmission and to investigate the possibility that the PLC signal can cross the power transformer itself. The new model is simpler than those previously proposed in literature, and it can be used in the whole frequency range available for NB PLC according to the CENELEC EN 50065-1 A-band. In order to validate the model, simulation and measurement results are compared for four oil-filled po…
An Innovative Measurement Approach for Load Flow Analysis in MV Smart Grids
2016
This paper proposes a novel measurement procedure for load flow analysis in medium voltage (MV) smart grids. The new approach is based on power measurements at low voltage (LV) side of MV/LV distribution substations. Such measurements are carried out by means of power quality analyzers. If compared with the load flow methods based on measurements at the MV side, the proposed approach has a lower cost and it offers an equally reliable measurement system. The proposed algorithm takes the basic concept of the current summation backward/forward method; some modifications are introduced to use LV load powers measurements. To this aim, the MV/LV power transformer is properly modeled and taken int…
A New Low Cost Coupling System for Power Line Communication on Medium Voltage Smart Grids
2018
This paper proposes and verifies the performance of an innovative and low cost coupling system for power line communication (PLC) on medium voltage (MV) smart grids. The coupling system makes use of the capacitive divider of the voltage detecting systems (VDSs) to inject and receive the PLC signal. VDS are usually already installed in the MV switchboards of the major electrical manufacturer all over the world according to IEC 61243-5. VDS are used to detect the presence of the mains voltage to guarantee personnel safety. An interface circuit has been developed to be connected between the PLC transceiver and the VDS socket. In this way, the PLC signal can be coupled to the MV network without…
Synchronization techniques for power quality instruments
2004
The measurement of voltage characteristics in power systems requires the accurate estimation of the power supply frequency and signal synchronization, even in the presence of disturbances. The authors developed and tested two innovative techniques for instrument synchronization. The first is based on signal spectral analysis techniques performed by means of the Chirp-Z transform analysis. The second is a phase-locked loop (PLL) software based on a time-domain coordinate transformation and an innovative phase-detection technique. To evaluate how synchronization techniques are adversely affected by the application of a disturbing influence, experimental tests were carried out, taking into acc…
New Measurement Procedure for Load Flow Evaluation in Medium Voltage Smart Grids
2013
The aim of this paper is to present a new approach for the medium voltage (MV) distribution network load flow analysis, mainly based on power measurement at the low voltage (LV) level of MV/LV distribution substations. This allows to use measurement instruments, usually already installed in the secondary substations, thus achieving an equally reliable measurement system with a lower cost compared to measurements at the MV side. The new approach can be applied using a proper communication system to collect the nodal measurements and an iterative algorithm based on ladder iterative technique (LIT) to compute the load flow. The validity of this method is presented and discussed on the basis of…
Co-evolution between trust in teachers and higher education toward digitally-rich learning environments
2017
Based on a powerful notion that the quality of higher education is crucial for innovation in digital economy and that such quality is subject to a conception of trust in teachers to deliver good education and advancement of information and communication technology (ICT), the dynamism of co-evolution between them was analyzed. Using a unique dataset representing the above system consisting of the rate of trust in teachers providing good education in the context of quality of education and their social status, of the level of higher education and the state of ICT advancement toward digitally-rich learning environments, an empirical numerical analysis of 20 countries was attempted. These count…
Economic evaluation of PV system for EV charging stations: Comparison between matching maximum orientation and storage system employment
2016
This article addresses the problem of the choice of a generation system to be implemented to reduce the impact of charging electric vehicles at University. Based on the behaviour of the student population, it is identified the electrical load. Two possible solutions are evaluated in order to manage the peak load: an orientation of the panels in order to increase the power at defined time and the use of storage system. The main strength and weakness points of two systems are investigated by taking into account the Levelized Cost of Energy.
Measurement Issues for the Characterization of Medium Voltage Grids Communications
2013
This paper is focused on the measurement issues and procedures for the characterization of medium voltage grids for narrowband power line communications (NB-PLCs), in the perspective of the use and integration of such technology into smart grids communication networks. The fundamentals are given for the characterization of the PLC channel, by means of noise and attenuation measurements. Suitable procedures are also developed for the characterization and modeling of the power system components in the frequency range of interest. Furthermore, the complete model of the PLC system is experimentally validated in a real case study.
CIGS PV Module Characteristic Curves Under Chemical Composition and Thickness Variations
2014
This paper analyzes how the electrical characteristics of a CIGS photovoltaic module are affected by the chemical composition and by the thickness variations of the CIGS absorber. The electrical characteristics here considered are the short circuit current, the open circuit voltage, the efficiency and the power peak. The chemical composition is varied by tuning the ratio between gallium and indium. This analysis has been performed by means of the wxAMPS software, developed by the University of Illinois. The above variations have been taken into account on a PV module made of 72 cells. This analysis has been carried out employing a PV module mathematical model developed and implemented by th…