Search results for "Smart Grid"
showing 10 items of 193 documents
A simplified approach for load flow analysis in MV smart grids based on LV power measurements
2017
This paper presents a simplified approach for load flow analysis in medium voltage (MV) distribution networks. It is a power summation Backward/Forward (B/F) algorithm, based on measurements of active and reactive powers at low voltage (LV) side of MV/LV distribution substations. The proposed solution allows achieving good accuracy, computational efficiency and fast convergence. In order to verify the algorithm performances, simulation studies are carried out in the case of a real test system, i.e. the distribution grid of Favignana Island (Mediterranean Sea, Italy). The compatibility between simulations results and power measurements at the MV bus bars of the generating substation shows th…
Scalable and Privacy-Preserving Admission Control for Smart Grids
2015
International audience; Energy demand and production need to be constantly matched in the power grid. The traditional paradigm to continuously adapt the production to the demand is challenged by the increasing penetration of more variable and less predictable energy sources, like solar photovoltaics and wind power. An alternative approach is the so called direct control of some inherently flexible electric loads to shape the demand. Direct control of deferrable loads presents analogies with flow admission control in telecommunication networks: a request for network resources (bandwidth or energy) can be delayed on the basis of the current network status in order to guarantee some performanc…
Secondary substation power line communications for medium voltage smart grids
2012
In this paper a performance analysis is carried out, in order to evaluate the possibility to employ power line communication (PLC) between secondary substations of a medium voltage (MV) distribution networks in a smart grid. The study is focused on the analysis of PLC technologies and the evaluation of the influence quantities on the communication performance in the most common case of by-pass connection at MV bus-bars of secondary substations. Different quantities have been analyzed as modulation techniques, requested bandwidth and bitrate, coupling device and system attenuation versus frequency in order to find the best solution for a reliable communication system. A complete model of a r…
Experimental investigation on PLC signal crossing of power transformers
2014
In this work the use of PLC in MV-LV networks is investigated, by means of experimental tests in the case of a two-ways MV/LV communication between two secondary substations. The two substations are connected by a MV overhead power line. Moreover each substation has a by-pass connection at MV bus-bars and a MV/LV power transformer. A ST7580 transceiver is used to inject the communication signal. The transceiver is embedded in a new interface device developed by the authors. In the paper the communication issues are introduced and some experimental tests are presented and discussed. Such tests have been carried out in the presence of voltage net, i.e. 24 kV, with the aim to verify the possib…
Smart district energy optimization of flexible energy units for the integration of local energy storage
2017
Several changes are involving electrical power systems, especially distribution networks. For this reason, the actors in charge of managing and operating reliably these grids are facing many technical issues regarding demand and supply balancing, Renewable Energy Sources and Electric Vehicles integration, peak load shaving, etc. In this context, many energy actions have been implemented for providing services to the power system managers by means of prosumers' demand and/or supply flexibility. This study reports the development of a centralized energy management solution for smart grids equipped with local storage devices, RES, consumers and other energy facilities in a district context. Th…
An Innovative Measurement Approach for Load Flow Analysis in MV Smart Grids
2016
This paper proposes a novel measurement procedure for load flow analysis in medium voltage (MV) smart grids. The new approach is based on power measurements at low voltage (LV) side of MV/LV distribution substations. Such measurements are carried out by means of power quality analyzers. If compared with the load flow methods based on measurements at the MV side, the proposed approach has a lower cost and it offers an equally reliable measurement system. The proposed algorithm takes the basic concept of the current summation backward/forward method; some modifications are introduced to use LV load powers measurements. To this aim, the MV/LV power transformer is properly modeled and taken int…
Large Scale Control of Deferrable Domestic Loads in Smart Grids
2016
International audience; In this paper, we investigate a realistic and low-cost deployment of large scale direct control of inelastic home appliances whose energy demand cannot be shaped, but simply deferred. The idea is to exploit 1) some simple actuators to be placed on the electric plugs for connecting or disconnecting appliances with heterogeneous control interfaces, including non-smart appliances, and 2) the Internet connections of customers for transporting the activation requests from the actuators to a centralized controller. Our solution requires no interaction with home users: in particular, it does not require them to express their energy demand in advance. A queuing theory model …
A New Low Cost Coupling System for Power Line Communication on Medium Voltage Smart Grids
2018
This paper proposes and verifies the performance of an innovative and low cost coupling system for power line communication (PLC) on medium voltage (MV) smart grids. The coupling system makes use of the capacitive divider of the voltage detecting systems (VDSs) to inject and receive the PLC signal. VDS are usually already installed in the MV switchboards of the major electrical manufacturer all over the world according to IEC 61243-5. VDS are used to detect the presence of the mains voltage to guarantee personnel safety. An interface circuit has been developed to be connected between the PLC transceiver and the VDS socket. In this way, the PLC signal can be coupled to the MV network without…
New Measurement Procedure for Load Flow Evaluation in Medium Voltage Smart Grids
2013
The aim of this paper is to present a new approach for the medium voltage (MV) distribution network load flow analysis, mainly based on power measurement at the low voltage (LV) level of MV/LV distribution substations. This allows to use measurement instruments, usually already installed in the secondary substations, thus achieving an equally reliable measurement system with a lower cost compared to measurements at the MV side. The new approach can be applied using a proper communication system to collect the nodal measurements and an iterative algorithm based on ladder iterative technique (LIT) to compute the load flow. The validity of this method is presented and discussed on the basis of…
Heuristic-Based Shiftable Loads Optimal Management in Smart Micro-Grids
2015
In this paper, an optimal power dispatch problem on a 24-h basis for distribution systems with distributed energy resources (DER) also including directly controlled shiftable loads is presented. In the literature, the optimal energy management problems in smart grids (SGs) where such types of loads exist are formulated using integer or mixed integer variables. In this paper, a new formulation of shiftable loads is employed. Such formulation allows reduction in the number of optimization variables and the adoption of real valued optimization methods such as the one proposed in this paper. The method applied is a novel nature-inspired multiobjective optimization algorithm based on an original…