0000000000026659

AUTHOR

Simone Giannini

Wireless partial discharge tracking on cross-linked polyethylene MV and HV cables

Medium voltage (MV)/high voltage (HV) cable lines are high-value assets and require substantial costs for their installation or replacement. For this reason, the capability to assess the condition of cable lengths and accessories on site is of great importance. Cross-linked polyethylene (XLPE) insulation is extensively used for MV, HV, and extra-high voltage (EHV) class cables [1] thanks to its excellent voltage-endurance and thermomechanical properties. In particular, XLPE-insulated cables feature substantially lower losses, easier manufacturing and jointing procedures, better environmental compatibility, and higher operating temperature compared with impregnated paper cables, which lead t…

research product

Critical issues in the PD testing methodology for XLPE-insulated MV cables: An experimental case

This paper describes some critical issues arising during the partial discharge (PD) testing of a 500m delivery length of an XLPE-insulated MV cable. At first, conventional PD measurements were performed on the whole length by using a standard acquisition system; PDs activity was detected, but the system allowed the operator to localize the PDs only on a length of 70 m. A visual inspection of this section highlighted the presence of an excoriation in the outer sheet. Aiming at a more accurate pin-pointing of the defect, more measurements were carried out in the proximity of the outer defect using a portable PD detection system. These measurements showed PDs activity, whose source was located…

research product