0000000000181167

AUTHOR

Mario Melodia

New solutions for prefabricated secondary substations in the view of sustainability

The secondary substations will assume an important role as “smart nodes” of the smart grid. So in few years there will be a widespread dissemination on the territory of this apparatus. Consequently, great care have to be taken not only on safety issues, but also on the constructive methodology, in order to determine low environmental impact and decommissioning cost. This paper focuses on innovative solutions for the realization of prefabricated secondary substations, in the direction of sustainability. Innovative layout and enclosure topologies have been here taken into account. In particular, by considering that the substation concrete box is, at the same time, uneconomical and with strong…

research product

Experimental EMF characterization of a secondary substation

This paper presents the results of the experimental EMC characterization of a new medium/low voltage (MV/LV) secondary substation, which was developed in the framework of the research project "NEW CAB ELARC". It has two MV/LV transformers, with total rated power of 1000 kVA. To perform the experimental characterization, firstly an analysis was performed of the Italian and European standards recommendations. Different approaches were highlighted and the most appropriate procedures were identified for the measurement of the magnetic fields emissions, at power systems frequency (50 Hz) in steady-state conditions. A dedicated test lab was set up for the secondary substation characterization. Th…

research product

A back to back method for the temperature rise test of prefabricated substations: A case study

In this work a back to back method is presented which allows to develop heating tests of prefabricated secondary substations with a limited number of supplying equipment (an induction regulator and a capacitor bank). The proposed method makes use of the transformer tap changers to create a voltage difference on the medium voltage side. In this way, only an adjunctive low voltage supply is needed. With the proposed test system, the heating tests are developed on a 1000 kVA prefabricated substation. Thanks to the experimental tests, the class of enclosure of the substation and the operating temperature and resistance of the power transformers are determined, according to the recommendations o…

research product