New solutions for prefabricated secondary substations in the view of sustainability

2016

The secondary substations will assume an important role as “smart nodes” of the smart grid. So in few years there will be a widespread dissemination on the territory of this apparatus. Consequently, great care have to be taken not only on safety issues, but also on the constructive methodology, in order to determine low environmental impact and decommissioning cost. This paper focuses on innovative solutions for the realization of prefabricated secondary substations, in the direction of sustainability. Innovative layout and enclosure topologies have been here taken into account. In particular, by considering that the substation concrete box is, at the same time, uneconomical and with strong…

Engineeringbusiness.industryprefabricated substationRenewable Energy Sustainability and the Environment020209 energyEnclosureEnergy Engineering and Power Technology02 engineering and technologyhuman exposureSettore ING-IND/32 - Convertitori Macchine E Azionamenti ElettriciNetwork topologyCivil engineeringConstructiveConstruction engineeringNuclear decommissioningSmart gridComputer Networks and CommunicationHardware and ArchitectureContainer (abstract data type)Sustainability0202 electrical engineering electronic engineering information engineeringEnvironmental impact assessmentdistance of first approximation (DPA)businesssmart grid
researchProduct

Experimental EMF characterization of a secondary substation

2015

This paper presents the results of the experimental EMC characterization of a new medium/low voltage (MV/LV) secondary substation, which was developed in the framework of the research project "NEW CAB ELARC". It has two MV/LV transformers, with total rated power of 1000 kVA. To perform the experimental characterization, firstly an analysis was performed of the Italian and European standards recommendations. Different approaches were highlighted and the most appropriate procedures were identified for the measurement of the magnetic fields emissions, at power systems frequency (50 Hz) in steady-state conditions. A dedicated test lab was set up for the secondary substation characterization. Th…

EngineeringElectromagnetic compatibility (EMC) secondary substations induction magnetic field electro-smogbusiness.industryElectrical engineeringSettore ING-IND/32 - Convertitori Macchine E Azionamenti ElettriciAutomotive engineeringInduction magnetic fieldlaw.inventionElectromagnetic compatibility (EMC)Electric power systemPower ratingElectro-smoglawSecondary substationsbusinessTransformerSettore ING-INF/07 - Misure Elettriche E ElettronicheLow voltage2015 AEIT International Annual Conference (AEIT)
researchProduct

A back to back method for the temperature rise test of prefabricated substations: A case study

2015

In this work a back to back method is presented which allows to develop heating tests of prefabricated secondary substations with a limited number of supplying equipment (an induction regulator and a capacitor bank). The proposed method makes use of the transformer tap changers to create a voltage difference on the medium voltage side. In this way, only an adjunctive low voltage supply is needed. With the proposed test system, the heating tests are developed on a 1000 kVA prefabricated substation. Thanks to the experimental tests, the class of enclosure of the substation and the operating temperature and resistance of the power transformers are determined, according to the recommendations o…

Engineeringbusiness.industryprefabricated substationRenewable Energy Sustainability and the EnvironmentElectrical engineeringpower transformerEnergy Engineering and Power TechnologyPower factorInduction regulatorSettore ING-IND/32 - Convertitori Macchine E Azionamenti ElettriciDistribution transformerTap changerAutomotive engineeringlaw.inventionlawEnergy efficient transformertemperature riseVoltage regulationheating testDelta-wye transformerbusinessTransformerSettore ING-INF/07 - Misure Elettriche E Elettroniche