EngineeringElectromagnetic compatibility (EMC) secondary substations induction magnetic field electro-smogbusiness.industryElectrical engineeringSettore ING-IND/32 - Convertitori Macchine E Azionamenti ElettriciAutomotive engineeringInduction magnetic fieldlaw.inventionElectromagnetic compatibility (EMC)Electric power systemPower ratingElectro-smoglawSecondary substationsbusinessTransformerSettore ING-INF/07 - Misure Elettriche E ElettronicheLow voltagedescription
This paper presents the results of the experimental EMC characterization of a new medium/low voltage (MV/LV) secondary substation, which was developed in the framework of the research project "NEW CAB ELARC". It has two MV/LV transformers, with total rated power of 1000 kVA. To perform the experimental characterization, firstly an analysis was performed of the Italian and European standards recommendations. Different approaches were highlighted and the most appropriate procedures were identified for the measurement of the magnetic fields emissions, at power systems frequency (50 Hz) in steady-state conditions. A dedicated test lab was set up for the secondary substation characterization. The measurement results showed that, thanks to the chosen layout, the emissions of the substation under test are lower than those of typical substations of the same power.
year | journal | country | edition | language |
---|---|---|---|---|
2015-10-01 | 2015 AEIT International Annual Conference (AEIT) |