An Improved Load Flow Method for MV Networks Based on LV Load Measurements and Estimations
A novel measurement approach for power-flow analysis in medium-voltage (MV) networks, based on load power measurements at low-voltage level in each secondary substation (SS) and only one voltage measurement at the MV level at primary substation busbars, was proposed by the authors in previous works. In this paper, the method is improved to cover the case of temporary unavailability of load power measurements in some SSs. In particular, a new load power estimation method based on artificial neural networks (ANNs) is proposed. The method uses historical data to train the ANNs and the real-time available measurements to obtain the load estimations. The load-flow algorithm is applied with the e…