Monitoring and energy performance assessment of an advanced DEC HVAC system in Morocco
This work addresses the energy performance of a solar Desiccant and Evaporative Cooling (DEC) system working with the freescoo technology. Freescoo is an innovative solar air conditioning concept for ventilation, cooling, dehumidification and heating of buildings in residential and tertiary sectors. The monitoring of the system started in November 2016 and will continue until the end of 2017. Energy performances are evaluated according to the monitoring procedure for solar cooling systems developed by the Task 38 and 48 of the International Energy Agency experts. The analysis based on monitoring data shows that, for typical operating conditions in cooling mode, the electricity saving in com…
Experimental results on adsorption beds for air dehumidification
Desiccant rotors are commonly used in large scale solar cooling open cycle applications. As is well known, adsorption heat sensibly reduces the dehumidification capacity of the desiccant material and results in lower system performance. The aim of this work is to describe an innovative solution that permits simultaneous mass and heat transfer. In particular, two components working with silica gel fixed beds were studied and compared. The first component is a simple packed bed containing silica gel grains. The second component is a fin and tube heat exchanger commonly used in several air conditioning applications wherein the spaces between the fins are filled with silica gel grains. In this …
Monitoring Results and Energy Performances Evaluation of Freescoo Solar DEC Systems
Abstract This work addresses the energy saving performances of some solar Desiccant and Evaporative Cooling (DEC) systems working with the freescoo technology. The innovative freescoo concept is based on the use two fixed and cooled adsorption beds and advanced indirect evaporative cooling processes. The main feature of this new adsorption bed concept is to allow the simultaneous dehumidification and cooling of air. The systems analyzed have been installed in Italy last here and results based on field monitoring data are here presented. A description of the monitored systems and comparisons between the energy performances based on the main performance indicators such as EER, thermal COP, co…