Disturbing Load Detection in Three-Wire and Four-Wire Systems Based on Novel Nonactive Powers From IEEE 1459-2000
Antonio CataliottiValentina Cosentinosubject
EngineeringTotal harmonic distortionSIMPLE (military communications protocol)business.industryPower system harmonicsElectrical engineeringAC powerharmonic distortion harmonic sources power quality power measurement power system harmonic power system measurementHarmonic analysisElectric power systemHarmonicElectronic engineeringElectrical and Electronic EngineeringbusinessSettore ING-INF/07 - Misure Elettriche E ElettronicheInstrumentationVoltagedescription
This paper presents an enhanced approach for the detection of disturbing loads in distorted and/or unbalanced three-phase power systems, both three-wire and four-wire. It is based on the IEEE Std. 1459-2000 effective apparent power resolution, and it requires only the separation of the fundamental components of voltage and current from the remaining harmonic content. In this paper, the formulation of the novel approach is given, and its effectiveness is discussed by means of several simulation tests, which were carried out on a simple test system.
year | journal | country | edition | language |
---|---|---|---|---|
2010-05-01 | IEEE Transactions on Instrumentation and Measurement |