Simple Circuit Models for Studying Global Earthing Systems

2007

The paper proposes three simple circuit models for the simulation of the behaviour of a global earthing system during different fault events. The models allow one the evaluation of the maximum earth potential rise at every possible fault location and for every possible fault event. The three considered fault events are: single-line-to-earth fault inside a MV/LV substation, double-earth-fault in a MV line, single-line-to-earth fault inside a HV/MV station. After having illustrated the hypotheses at the basis of the study, the circuit models for the three fault events are presented and a numerical example shows how to use them in order to check the "global safety" of the interconnected earthi…

EngineeringEarth potential riseGroundbusiness.industryHardware_PERFORMANCEANDRELIABILITYEarthing systemFault (power engineering)Line (electrical engineering)Fault indicatorReliability engineeringStuck-at faultSettore ING-IND/33 - Sistemi Elettrici Per L'EnergiaGrounding Earth Circuit faults Substations Electrodes Integrated circuit interconnections Voltage Safety Paramagnetic resonance Fault locationFault modelbusiness
researchProduct

Experimental EMF characterization of a secondary substation

2015

This paper presents the results of the experimental EMC characterization of a new medium/low voltage (MV/LV) secondary substation, which was developed in the framework of the research project "NEW CAB ELARC". It has two MV/LV transformers, with total rated power of 1000 kVA. To perform the experimental characterization, firstly an analysis was performed of the Italian and European standards recommendations. Different approaches were highlighted and the most appropriate procedures were identified for the measurement of the magnetic fields emissions, at power systems frequency (50 Hz) in steady-state conditions. A dedicated test lab was set up for the secondary substation characterization. Th…

EngineeringElectromagnetic compatibility (EMC) secondary substations induction magnetic field electro-smogbusiness.industryElectrical engineeringSettore ING-IND/32 - Convertitori Macchine E Azionamenti ElettriciAutomotive engineeringInduction magnetic fieldlaw.inventionElectromagnetic compatibility (EMC)Electric power systemPower ratingElectro-smoglawSecondary substationsbusinessTransformerSettore ING-INF/07 - Misure Elettriche E ElettronicheLow voltage2015 AEIT International Annual Conference (AEIT)
researchProduct

On the hazardous situations due to the presence of HV/MV substations in urban areas

2017

The paper focuses on the hazardous situations that can rise in urban areas in case of earth fault inside a High Voltage/Medium Voltage station. IEEE and IEC/EN Standards and technical documents are examined and discussed, in order to propose some practical guidelines for a safe integration of such installations in contexts characterized by the presence of low voltage systems and not trained persons.

EngineeringEnvironmental Engineeringbusiness.industry020209 energySubstationsElectrical engineeringEnergy Engineering and Power Technology02 engineering and technologySubstationTechnical documentationIndustrial and Manufacturing EngineeringSettore ING-IND/33 - Sistemi Elettrici Per L'EnergiaEarth fault; Global Earthing Systems; Safety; Substations; electrical safetyHazardous wasteOrder (business)Global Earthing Systems0202 electrical engineering electronic engineering information engineeringElectrical and Electronic EngineeringSafetyelectrical safetybusinessLow voltageEarth faultGlobal Earthing SystemVoltage
researchProduct

The Quest for Global Safety

2007

The authors present a systematic study on the factors that have influence on the establishment of the safety conditions ensuring the rise of Global Earthing Systems. Starting from the definition of Global Earthing System given by CENELEC Document HD 637 SI and from the results of the studies done on the last years on the interconnected earthing systems inside MV networks, the paper proposes some directions of deepening on the topic of Global Safety. Some of the themes whom the paper deals with are: the correct definition of proximity, interconnection and quasi-equipotentiality of the earth electrodes belonging to a Global Earthing System; the influence of the presence of HV/MV stations on h…

EngineeringInterconnectionbusiness.industryGroundElectrical engineeringEarthing systemFault (power engineering)Reliability engineeringlaw.inventionSettore ING-IND/33 - Sistemi Elettrici Per L'EnergialawCLARITYGrounding Earth Electrodes Substations Voltage High definition video Satellite ground stations Enterprise resource planning Electrical safety Electrical accidentsbusiness
researchProduct

New Measurement Procedure for Load Flow Evaluation in Medium Voltage Smart Grids

2013

The aim of this paper is to present a new approach for the medium voltage (MV) distribution network load flow analysis, mainly based on power measurement at the low voltage (LV) level of MV/LV distribution substations. This allows to use measurement instruments, usually already installed in the secondary substations, thus achieving an equally reliable measurement system with a lower cost compared to measurements at the MV side. The new approach can be applied using a proper communication system to collect the nodal measurements and an iterative algorithm based on ladder iterative technique (LIT) to compute the load flow. The validity of this method is presented and discussed on the basis of…

EngineeringIterative methodbusiness.industrypower system measurementSystem of measurementSmart grid (SG) power system measurements load flow power quality analyzer (PQA) state estimation (SE) advanced metering infrastructure (AMI)substations.Communications systemautomatic meter readingpower distribution reliabilityPower (physics)Settore ING-IND/33 - Sistemi Elettrici Per L'Energiasmart power gridsSmart gridElectronic engineeringload flowiterative methodsPower-flow studybusinessLow voltageSettore ING-INF/07 - Misure Elettriche E ElettronicheVoltagepower system state estimation
researchProduct

Legal Liability of Professional Engineers: The Case of a Fire at a Shopping Center

2019

In this paper, the authors discuss the legal liabilities of the professional engineer as both the engineer of record of a project and the construction site manager. In particular, this paper analyzes the case of a fire at an end-user MV/LV substation of a shopping center in Italy, occurred a few years after maintenance works on the electrical installation. The professional engineer who had designed and overseen the construction of the substation was accused of criminal negligence. The authors through the examination of applicable technical standards, as well as of safety regulations, demonstrate that the professional engineer had acted diligently and that there was no ground for the neglige…

EngineeringLegal liabilitybusiness.industrySubstationsSite managerTechnical standardForensic EngineeringLegal liabilitySettore ING-IND/33 - Sistemi Elettrici Per L'EnergiaSettore ING-IND/31 - ElettrotecnicaDocumentationProfessional EngineerElectrical installationEngineering ethicsCenter (algebra and category theory)businessElectric FireCriminal negligenceChain of custody
researchProduct

Ground-Fault Current Transfer at the Transition Station of a Combined Overhead-Cable Line. A Parametric Analysis

2007

When a substation is fed by a combined overhead-cable transmission line, a significant part of the ground fault current flows through the grounded cable sheaths and discharges into the earth at the transition station, where cables are connected to the overhead line. If the transition station is a dead-end steel pole structure, the local ground electrode, small and of high resistance, could be inadequate to maintain the ground potential rise within safety limits in case of a fault to ground at the receiving end substation. Based on a circuit model approach, the paper presents a parametric analysis of the fault current distribution between the faulted substation and the transition station, ta…

EngineeringParametric analysisbusiness.industryElectrical engineeringFault (power engineering)Line (electrical engineering)law.inventionSettore ING-IND/33 - Sistemi Elettrici Per L'EnergiaTransmission linelawTransfer (computing)Overhead cableSubstations Fault currents Circuit faults Power overhead lines Power cables Cable shielding Satellite ground stations Steel Electrodes SafetyCurrent (fluid)businessComputer Science::Operating SystemsOverhead line
researchProduct

Fall of Potential Measurement of the Earth Resistance in Urban Environments: Accuracy Evaluation

2019

Both Standards EN 50522 and IEEE 81 propose the fall of potential method (FPM) to carry out the measurement of the resistance to earth ( $R_{\text{ES}}$ ) of an earthing system (ES). However, in urban areas, the recommended distances between the ES and auxiliary electrodes are not easy to respect, due to the presence of buildings and tarmac. Furthermore, unknown buried metallic parts and interconnections among ESs could modify the earth potential profile of the area, affecting the measurement results. In this paper, the key-issues that influence the measured $R_{\text{ES}}$ when the FPM is used in an urban environment are presented. A parametric analysis, carried out with Comsol Multiphysic…

Field (physics)Computer science020209 energyMultiphysicsSubstationsurban areas02 engineering and technologyEarth GroundingTopologyfall of potentialIndustrial and Manufacturing Engineering0202 electrical engineering electronic engineering information engineeringGround resistance measurementElectrical and Electronic EngineeringMV/LV substationElectrodesGroundingTarmacresistance measurementGround020208 electrical & electronic engineeringPotential methodEarthPotential measurementEarthing systemSettore ING-IND/33 - Sistemi Elettrici Per L'EnergiaSettore ING-IND/31 - ElettrotecnicaEarth Electrodes Grounding Electric potential Substations Probes Ground resistance measurementElectric potentialControl and Systems EngineeringProbesElectric potential
researchProduct

Safety Concerns on Ground Fault Application Transfer Phenomenon in HV Installations

2007

When a fault to ground occurs in HV/MV substations supplied by a combined overhead-cable line, most of the fault current can be transferred and injected into the soil several kilometers far away from the fault location. This phenomenon is called "fault application transfer" and mostly concerns transition stations, where cables are connected to the overhead line. If the transition station is a dead-end steel pole structure, usually accessible to the general public, the local ground electrode could be inadequate to maintain ground potential rise within safety limits. Hence, dangerous touch and step voltages may appear at exposed locations. In the paper results of various computer simulations …

Settore ING-IND/33 - Sistemi Elettrici Per L'EnergiaEngineeringTransfer phenomenonbusiness.industryGroundTransfer (computing)Electrical engineeringSafety Substations Fault currents Soil Fault location Cables Steel Electrodes Voltage Computer simulationbusinessFault (power engineering)Overhead lineLine (electrical engineering)Voltage2007 IEEE Symposium on Product Compliance Engineering
researchProduct

A study of the behaviour of earth electrodes connected together in resonant earthed neutral systems

2005

Inside urban areas the earth electrodes of the MV/lv substations are often electrically connected together so as to form a single extended earthing system. The advantages of the realization of an extended earthing system are the reduction of the current that each substation earth electrode injects in the soil during the fault and a better uniformity of the voltages to earth inside the urban area. In previous works, models for the study of extended earthing systems have been proposed. These models were valid for the case of single-line-to earth fault in isolated neutral MV networks. In this paper, the extended earthing system is analyzed in the case of a resonant earthed neutral MV network. …

resonant earthed neutral systeminterconnected earthing systemextended earthing systemMV/lv substations.
researchProduct