6533b82afe1ef96bd128cbee

RESEARCH PRODUCT

Partial Discharges Diagnostics Along Medium Voltage Cables

A. ImburgiaPietro RomanoL. De Rai

subject

Materials scienceRenewable Energy Sustainability and the Environmentbusiness.industryAcousticsPD MeasurementDetectordiagnosticEnergy Engineering and Power TechnologyComputer Science Applications1707 Computer Vision and Pattern RecognitionRotationSignalIndustrial and Manufacturing Engineeringantenna sensorpartial dischargeSettore ING-IND/31 - ElettrotecnicaComputer Networks and CommunicationIntelligent sensorArtificial IntelligencePartial dischargeWirelessPower cablebusinessInstrumentationVoltage

description

In the last years different partial discharge (PD) measuring techniques have been developed because PD diagnostic is the most widely tool to evaluate the insulation condition of a power cable. Recently non-conventional methods and sensors have been used in order to reach improved results in PD measurements. New sensors based on wireless technology were developed in order to simplify PD measurement especially for on-line, on-site diagnosis. The purpose of this work is to perform measurements that allow to study the variation of pulses when they travel along a medium voltage cable and characterize a new smart PD source detector and locator, named Wings sensor. For these purposes, internal PD signals have been acquired and compared with those detected by the dassical PD acquisition system. In addition, the characterization of the Wings sensor has been completed by acquiring PD pulses when the sensor is placed at different rotation angle and distance from the cable. It was found that for a better voltage magnitude signal the sensor should be placed in parallel with the cable and in contact with it.

https://doi.org/10.1109/rtsi.2018.8548443