6533b823fe1ef96bd127edd1

RESEARCH PRODUCT

A Technique for Power Supply Harmonic Impedance Estimation Using a Controlled Voltage Disturbance

Pericle ZanchettaMark SumnerB. PalethorpeDavid ThomasM. C. Di Piazza

subject

Engineeringindustrial power systemsSwitched-mode power supplybusiness.industryImpedance measurementImpedance bridgingHardware_PERFORMANCEANDRELIABILITYVoltage optimisationpower qualityElectric power systempower system measurements.Power electronicsElectronic engineeringVoltage sourceElectrical and Electronic EngineeringbusinessActive filterNegative impedance converter

description

A method for power system impedance estimation is presented. The method employs a power converter to inject a voltage transient onto the supply system. As the technique employs controlled power electronic devices it may be used as a stand alone piece of a portable measurement equipment, or it may be embedded into the functions of an active shunt filter for improved harmonic control. The impedance is estimated through correlation of the measured voltage and current transients. Simulations and experimental results demonstrate the measurement technique is highly accurate and effective.

10.1109/63.988831https://publications.cnr.it/doc/52500